Case: T08FR00712

Parcel: 13411363J


Addresses:

7909 E 22ND ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00712

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2008 INSP - FULL Approved
03/14/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Open wires on light fixture in break room.
TFC REFERENCE: 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
REQUIRED CORRECTION: Replace light fixture or have qualified individual repair.

___2. PROBLEM: Portable fire extinguisher on floor and has no service tag.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed. AND: 906.7 Hangers and brackets. Hand-held portable fire
extinguishers, not housed in cabinets, shall be installed on the
hangers or brackets supplied. Hangers or brackets shall be
securely anchored to the mounting surface in accordance with
the manufacturer’s installation instructions.
REQUIRED CORRECTION: Have portable fire extinguisher serviced and placed on a bracket or remove from premises.

___3. PROBLEM: Green extension cord leading to small fountain.
TFC REFERENCE: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring.
REQUIRED CORRECTION: Plug fountain directly into outlet or use approved power strip..

___4. PROBLEM: Orange extension cord (?) appears to be coming out of ground. This cord leads to an outdoor fountain.
TFC REFERENCE:605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with portable appliances.
REQUIRED CORRECTION: Must plug fountain directly into outlet or power strip. Cord cannot be buried directly under soil. Cord must be protected from environmental damage. May run through conduit.

___5. PROBLEM: Exterior outlet lacks weather proof cover.
TFC REFERENCE605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
REQUIRED CORRECTION: Exterior outlet needs weather proof cover.

___6. PROBLEM: Ceiling dry wall missing in some spots allowing the passage of smoke and flames into the attic above the ceiling.
TFC REFERENCE: 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops,
shaft enclosures, partitions, smoke barriers, floors, fire-resistive
coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems) shall be
maintained. Such elements shall be properly repaired, restored
or replaced when damaged, altered, breached or penetrated.
Openings made therein for the passage of pipes, electrical conduit,
wires, ducts, air transfer openings and holes made for any
reason shall be protected with approved methods capable of
resisting the passage of smoke and fire.
REQUIRED CORRECTION: Replace missing drywall to ceiling. If you decide to tear all the drywall off the ceiling in the store area then you must get a permit first. Seal off the rest of the rafter area above the offices as well.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

_X__Approved

___Not Approved