Case: T08FR00710

Parcel: 13409018B


Addresses:

8578 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00710

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/15/2008 INSP - FULL Approved
03/13/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Compressed gas tanks in break room are unsecured.
TFC REFERENCE: 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity.
REQUIRED CORRECTION: Secure compressed gas cylinders against the danger of falling.

___2. PROBLEM: Double door exits with double key lock need sign above door indicating that door is to remain unlocked while building is occupied.
TFC REFERENCE: 1008.1.8.3 Locks and latches. 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background,
REQUIRED CORRECTION: Have required signage placed above both doors.

___3. PROBLEM: Certificate of Occupancy not posted.
TFC RFERENCE: 105.3.5 Posting the permit. Issued permits shall be kept on the premises designated therein at all times and shall be readily available for inspection by the fire code official.
REQUIRED CORRECTION: Have Certificate of Occupancy posted in a readily visible location for inspection by fire code official.

___4. PROBLEM: Paper work for maintenance on hood suppression system not available for fire inspector to examine.
TFC REFERENCE: 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request.
REQUIRED CORRECTION: Maintain copies of all service performed on hood system. Keep these records on the premises for inspection by the fire code official.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

__X_Approved

___Not Approved