Case: T08FR00696

Parcel: 13101014H


Addresses:

1440 S CRAYCROFT RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
04/08/2008 INSP - FULL Approved All items corrected.
03/21/2008 INSP - FULL Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
___ Remove double keyed lock from south courtyard exit door.
03/21/2008 INSP - FULL Correction Required 907.2.10.1.1 Group R-1. Single- or multiple-station smoke alarms shall be installed in all of the following locations in Group R-1:
1. In sleeping areas.
2. In every room in the path of the means of egress from the sleeping area to the door leading from the sleeping unit.
___All rooms must have smoke alarms installed and functional. It is the responsibility of business owner to ensure all rooms have functioning smoke detectors.
03/12/2008 INSP - FULL Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated.
___Repair drywall in water heater closet of maintenance room.
03/12/2008 INSP - FULL Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
___Replace smoke detectors in rooms 225 & 223. Inventory, inspection and testing of detectors is to be conducted monthly and a log kept on-site.
03/12/2008 INSP - FULL Correction Required 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
___Open wires need to be properly capped and in junction box.