Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T08FR00682

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
03/11/2008 INSP - FULL Violation 1.) TFC 1008.1.8.3 A READILY VISIBLE SIGN MUST BE POSTED ON THE EGRESS SIDE OF THE MAIN ENTRY DOOR STATING: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THIS SIGN MUST BE IN LETTERS 1 INCH HIGH ON A CONTRASTING BACKGROUND.
03/11/2008 INSP - FULL Violation 2.) TFC 605.4 THE MULTI-PLUG ADAPTOR IN THE BOOTH AT THE FRONT OF THE STORE NEEDS TO BE REPLACED WITH A UL LISTED FUSIBLE POWER STRIP.

3.) TFC 605.6 THE ELECTRICAL CORD FOR THE LIGHT AT THE FRONT COUNTER NEEDS TO BE REPLACED. NO OPEN WIRING SPLICES IS ALLOWABLE.

4.) TFC 605.1 PERMANENT ELECTRICAL WIRE FOR OUTLET LOCATED AT THE DOORWAY FOR THE BACK ROOM MUST BE ENCLOSED IN CONDUIT.
03/11/2008 INSP - FULL Violation
03/11/2008 INSP - FULL Violation 3.) TFC 605.6 THE ELECTRICAL CORD FOR THE LIGHT AT THE FRONT COUNTER NEEDS TO BE REPLACED. NO OPEN WIRING SPLICES ARE ALLOWABLE.
03/11/2008 INSP - FULL Violation 4.) TFC 605.1 PREMANENT ELECTRICAL WIRE FOR OUTLET LOCATED AT THE DOOR WAY FOR THE BACK ROOM MUST BE ENCLOSED IN CONDUIT.
03/11/2008 INSP - FULL Violation 5.) TFC 1008.1.8 METAL STRAPS USED FOR A SLIDE BAR LOCK AT REAR DOOR MUST BE REMOVED.