Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2008 | VIOL - MEANS OF EGRESS | Approved | ||
| 03/10/2008 | VIOL - MEANS OF EGRESS | Violation | Emergency lighting: IFC2006 [TFC with modifications] / 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. |
|
| 03/10/2008 | VIOL - MEANS OF EGRESS | Violation | Exit signs not lit: IFC2006 [TFC with modifications] / 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____Fix light in exit signs. |