Case: T08FR00652

Parcel: 128010040


Addresses:

5890 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00652

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/13/2008 INSP - FULL Approved All Items Corrected
03/11/2008 INSP - FULL Correction Required 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly.
___ Bring height of storage down in Eileen Fisher fitting room storage, and organize such that access may be made to rear of storage area.
03/11/2008 INSP - FULL Correction Required 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.
___Bring stock heights below 18" from sprinkler heads through out store. Specific Areas : Eileen Fisher Fitting Room storage corridor, Men's stock room, Origins stock room, Women's shoes stock room, Estee Lauder escalator (shelving blocking spray pattern)
03/11/2008 INSP - FULL Correction Required 1014.4.1 Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches (914 mm). Exception: Nonpublic aisles serving less than 50 people
and not required to be accessible by Chapter 11 of the International Building Code need not exceed 28 inches (711 mm) in width.
___Maintain clear aisles in Origins stock room.
03/11/2008 INSP - FULL Correction Required 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording.
___Label outside door to main electrical room.
03/11/2008 INSP - FULL Correction Required 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern.
___Provide proper coverage in all door closets for Mall. Remove all combustibles from closets until coverage is provided.
03/11/2008 INSP - FULL Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained.
___Repair drywall in Children's water heater room.
___Repair drywall in Women's shoe stock room.
___Repair/Cover access hole in ceiling of Mall Door closets.
03/11/2008 INSP - FULL Correction Required 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms.
___Remove stock from Children's water heater room.
03/11/2008 INSP - FULL Correction Required 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.
___Clear storage in front of Men's Denim Electrical area.
03/11/2008 INSP - FULL Correction Required 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
___Label Riser Room Door.
03/11/2008 INSP - FULL Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
___Have Fire Alarm system tested and inspected.