Case: T08FR00629

Parcel: 12110005D


Addresses:

4766 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00629

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/25/2008 INSP - FULL Approved ALL NOTED SPRINKLER SYSTEM DEFECIENCIES HAVE BEEN CORRECTED. 06/25/08
03/05/2008 INSP - FULL Correction Required TFC 901.4
1.) LOWER SPRINKLER HEAD OUTSIDE OF BREAKROOM SO THAT IT EXTENDS THROUGH CEILING TILE.

2.) RELOCATE OR ADD HEAD ABOVE BOX CRUSHER.

3.) LOCATE SPRINKLER HEADS AS REQUIRED TO MAINTAIN PROPER COVERAGE AT THE ENTRANCE TO STOCK ROOM.

4.) REPLACE SPRINKLER HEAD IN MEN'S ROOM IF PAINTED.

5.) SPRINKLER HEAD COVERAGE UNDER CANOPY OUTSIDE THE FRONT OF STORE REQUIRED.
03/05/2008 INSP - FULL Correction Required TFC 315.2.3

CLEAN UP STORAGE IN MECHANICAL ROOM TO ALLOW 3 FEET CLEARANCE FROM EQUIPMENT.