Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR00629
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2008 | INSP - FULL | Approved | ALL NOTED SPRINKLER SYSTEM DEFECIENCIES HAVE BEEN CORRECTED. 06/25/08 | |
03/05/2008 | INSP - FULL | Correction Required | TFC 901.4 1.) LOWER SPRINKLER HEAD OUTSIDE OF BREAKROOM SO THAT IT EXTENDS THROUGH CEILING TILE. 2.) RELOCATE OR ADD HEAD ABOVE BOX CRUSHER. 3.) LOCATE SPRINKLER HEADS AS REQUIRED TO MAINTAIN PROPER COVERAGE AT THE ENTRANCE TO STOCK ROOM. 4.) REPLACE SPRINKLER HEAD IN MEN'S ROOM IF PAINTED. 5.) SPRINKLER HEAD COVERAGE UNDER CANOPY OUTSIDE THE FRONT OF STORE REQUIRED. |
|
03/05/2008 | INSP - FULL | Correction Required | TFC 315.2.3 CLEAN UP STORAGE IN MECHANICAL ROOM TO ALLOW 3 FEET CLEARANCE FROM EQUIPMENT. |