Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T08FR00605
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2008 | VIOL - MEANS OF EGRESS | Approved | ||
| 03/03/2008 | VIOL - MEANS OF EGRESS | Violation | Emergency lighting: IFC2006 [TFC with modifications] / 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. |
|
| 03/03/2008 | VIOL - MEANS OF EGRESS | Violation | Double keyed lock on door: IFC2006 [TFC with modifications] / 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ______ Remove keyed dead bolts on all exterior doors. [Dishroom interior door is ok because it has its own exit.] |
|
| 03/03/2008 | VIOL - MEANS OF EGRESS | Violation | Exit sign not lit: IFC2006 [TFC with modifications] / 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____Fix light in exit sign. |