Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2008 | VIOL - BUILDING SVCS & SYSTEMS | Approved | -Abated, approved 3/13. | |
| 02/29/2008 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | ____Extension cords used in place of permanent wiring. (day rooms) 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 605.4.1 Power tap design Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ***Remove all extension cords, install power taps as referenced above. (all throughout house) |