Case: T08FR00577

Parcel: 12701005D


Addresses:

5151 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00577

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
07/24/2008 INSP - FULL Approved
02/29/2008 INSP - FULL Violation 1). Fire drill shall be conducted. Please inform fire department of date by 4-2-08. IFC 404
2). Update emergency contact information lock box. IFC 404
3). Trouble light is indicated on fire alarm panel in elevator room. This shall be repaired. IFC 901.6
4). Emergency generator log showing start up times shall be submitted. IFC 604.3.2
5). 16th floor. El Paso Gas. Portable fire extinguisher shall be mounted and serviced. IFC 901.6
6). 11th floor. Lennar Suite: Currently stock is obstructing water flow from sprinkler system .All stock shall be removed 2 feet from ceiling. IFC 901.6,
7). Repair electrical faceplates on 9th floor IFC 605.1
8). Storage of non used furniture shall be orderly.1st floor warehouse.
IFC 315