Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR00569
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/21/2008 | INSP - FULL | Approved | All items corrected | |
02/29/2008 | INSP - FULL | Correction Required | IFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. ___Maintain 18" clearance throughout all areas. (Visuals rooms, 2nd floor; Stock room, Charter Club; Visuals, Beauty Salon; Show window display areas) |
|
02/29/2008 | INSP - FULL | Correction Required | IFC 703.4 Testing. Horizontal and vertical sliding and rolling fire doors shall be inspected and tested annually to confirm proper operation and full closure. A written record shall be maintained and be available to the fire code official. ___Roll up fire door on 2nd floor to be inspected and tested annually. (alterations, by breakroom). ___Horizontal sliding doors by bundler machine to be inspected and tested annually. (loading dock) |
|
02/29/2008 | INSP - FULL | Correction Required | IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. ___Replace ceiling tiles (Beauty Salon, Men's stock area) ___Close ceiling hatch access door (Alterations) |
|
02/29/2008 | INSP - FULL | Correction Required | IFC 1014.4.1 Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches (914 mm). Exception: Nonpublic aisles serving less than 50 people and not required to be accessible by Chapter 11 of the International Building Code need not exceed 28 inches (711 mm) in width. ___Maintain clear aisle width (Stock room, Charter Club; Visuals in Beauty Salon/Hallway) |
|
02/29/2008 | INSP - FULL | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ___Provide current Annual Sprinkler & Alarm reports. ___Maintain/clean sprinkler head in Visuals room - 2nd floor. |
|
02/29/2008 | INSP - FULL | Correction Required | IFC 315.2.2 Means of egress. Combustible materials shall not be stored in exits or exit enclosures. ___Remove combustibles from beneath Southeast stairwell. |
|
02/29/2008 | INSP - FULL | Correction Required | IFC 703.2 Opening protectives. Opening protectives shall be maintained in an operative condition in accordance with NFPA 80. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable. Fusible links shall be replaced promptly whenever fused or damaged. Fire door assemblies shall not be modified. IFC 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position. ___ 3 Fire doors on second floor by freight elevator are not to be blocked open. Double door hardware needs to be replaced so door will latch automatically. |
|
02/29/2008 | INSP - FULL | Correction Required | IFC 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. ___Remove combustibles from equipment rooms (doors in Southeast Electrical room). |
|
02/29/2008 | INSP - FULL | Correction Required | IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ___Provide cover for J-boxes (2) in Southside Window Display. |
|
02/29/2008 | INSP - FULL | Correction Required | IFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. ___Clear exits in front of doors in Loading Dock (sliding fire doors and from offices to loading dock**). **If lock to be installed on door from offices, must be operable from inside without key or special knowledge. |