Case: T08FR00565

Parcel: 119180800


Addresses:

3640 S 16TH AV


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T08FR00565

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
05/28/2008 VIOL - BUILDING SVCS & SYSTEMS Approved Approved.
02/27/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required ____Electrical panels blocked. (Behind customer service desk)

605.3 Working space and clearance
A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space.

***Keep ALL electrical panels clear at all times.
02/27/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required ____Extension cords in use use, routed around doorway, piggybacked electrical cords. (Pharmacy)

605.5 Extension cords
Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

***Remove extension cords, plug power tap directly into wall receptacle, no piggybacking of electrical cords allowed.