Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T08FR00565
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/28/2008 | VIOL - BUILDING SVCS & SYSTEMS | Approved | Approved. | |
02/27/2008 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | ____Electrical panels blocked. (Behind customer service desk) 605.3 Working space and clearance A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space. ***Keep ALL electrical panels clear at all times. |
|
02/27/2008 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | ____Extension cords in use use, routed around doorway, piggybacked electrical cords. (Pharmacy) 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. ***Remove extension cords, plug power tap directly into wall receptacle, no piggybacking of electrical cords allowed. |