Case: T08FR00563

Parcel: 13338005E

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00563

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
03/18/2008 INSP - FULL Approved
02/26/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Inspection tag on portable fire extinguisher shows last inspection/servicing was in 2006.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.
REQUIRED CORRECTION: Have portable fire extinguisher serviced by a qualified professional.

___2. PROBLEM: Portable fire extinguisher is not mounted on a bracket.
TFC REFERENCE: 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the
hangers or brackets supplied. Hangers or brackets shall be
securely anchored to the mounting surface in accordance with
the manufacturer’s installation instructions.
REQUIRED CORRECTION: Have fire extinguisher mounted on an approved bracket.

___3. PROBLEM: Sprinkler head above bread tray has intermittent leak per employee observation. Not leaking or wet at time of inspection.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective.
REQUIRED CORRECTION: Have qualified individual inspect and repair sprinkler head.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

_X__Approved

___Not Approved