Case: T08FR00555

Parcel: 11707270A


Addresses:

555 E 18TH ST


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T08FR00555

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
02/26/2008 INSP - FULL Violation 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
Remove all items from in front of Panels.
02/26/2008 INSP - FULL Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an operative
condition at all times, and shall be replaced or repaired
where defective. Nonrequired fire protection systems and
equipment shall be inspected, tested and maintained or removed.
Bring all stand pipes and alarms up to code.