| 04/15/2008 | INSP - FULL | Approved | All Items Corrected | |
| 02/21/2008 | INSP - FULL | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Repair gas valve and pulley on rear hood system. ____Replace nozzle covers. ____Have all fire extinguishers inspected. |
|
| 02/21/2008 | INSP - FULL | Correction Required | 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ____Repair all illuminated Exit signs and Emergency lighting. |
|
| 02/21/2008 | INSP - FULL | Correction Required | 1027.8 Opening force for doors. The opening force for interior side-swinging doors without closers shall not exceed a 5-pound (22 N) force. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a force of not more than 15 pounds (66 N). The door shall be set in motion when subjected to a force not exceeding a 30-pound (133 N) force. The door shall swing to a full-open position when subjected to a force of not more than 50 pounds (222 N). Forces shall be applied to the latch side. ____Repair exit in rear dining area. |
|
| 02/21/2008 | INSP - FULL | Correction Required | 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. ____Secure all CO2 cylinders. |