Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR00507
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2008 | INSP - FULL | Approved | approved | |
02/20/2008 | INSP - FULL | Violation | 1). Fire drill required. Date to be determined by 3-19-08 IFC 404.2 2). Fire pump test report due IFC 901.6 3) Re-rack and maintain standpipe hose on roof. Currently not properly racked. IFC 901.6 4). All plastic and combustible material shall be removed from mech/air handler rooms. IFC 315.2.3 5). Currently in 6th floor phone room, 6th floor janitor closet there are holes in ceiling. These shall be repaired. IFC 703.1 6). Suite 400: power supply near desk: all power taps shall be plugged directly into wall. IFC 605.4.2 7). Replace signs near elevator stating: shall read: IN FIRE EMERGENCY, DO NOT USE ELEVATOR. USE EXIT STAIRS. Where they are worn. This letter is to inform you that abatement of these Tucson Fire Code violations must be completed by 3-19-08. |