Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/08/2008 | VIOL - BUILDING SVCS & SYSTEMS | Approved | Approved. | |
| 02/22/2008 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | ___Extension cords used in place for permanent wiring. (all throughout store) 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. ***Replace ALL extension cords with UL approved power taps, with overcurrent protection, plugged directly to a permanent receptacle. |
|
| 02/22/2008 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | ___Various outlets need covers, as well as electrical boxes. (all throughout store.) 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers ***Repair ALL missing covers. |
|
| 02/22/2008 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | ___power cords piggybacked, powertaps not plugged into permanent receptacles, cords affixed to ceililng, walls. Multiplug adapters without overcurrent protection in use. 605.4 Multiplug adapters Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC electrical code shall be prohibited. 605.4.1 Power tap design Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ***Replace all unapproved wiring per the Tucson Fire Code and ICC Electrical Code. |