Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T08FR00500

Parcel: 136100940


Addresses:

2601 S HOUGHTON RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00500

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
03/05/2008 INSP - FULL Approved
02/19/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Tag on sprinkler riser and inspectors test valve show last test and service of system was11/06.
TFC REFERENCE: 901.6.1 Standards. Fire protection systems shall be inspected, tested and maintained...
REQUIRED CORRECTION: Have sprinkler system tested yearly and tagged as having been tested on what month and year.

___2. PROBLEM: Access to fire extinguisher in pharmacy and in warehouse blocked or hampered.
TFC REFERENCE: 906.6 Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view.
REQUIRED CORRECTION: Keep portable fire extinguishers visible and free of obstructions.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

_X__Approved

___Not Approved