Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T08FR00488

Parcel: 12401002B


Addresses:

1339 E 1ST ST

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
03/07/2008 VIOL - MEANS OF EGRESS Approved O.K. 3/4.
02/15/2008 VIOL - MEANS OF EGRESS Correction Required ____Exit sign out of service. (between rooms 28-29)

1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section
2702 of the International Building Code

***Repair exit sign to full working order.
02/15/2008 VIOL - MEANS OF EGRESS Correction Required ___Emergency lighting not functioning, out of aim. (chapter room)

1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system.

***Repair emergency lighting to full function, and ensure all emergency lighting is aimed downward to ensure illumination of egress pathway during an emergency.
02/15/2008 VIOL - MEANS OF EGRESS Correction Required ____Curtains blocking exit doors (2) in dining area.

1028.5 Furnishings and decorations. Furnishings, decorations or other objects shall not be placed so as to obstruct exits, access thereto, egress therefrom, or visibility thereof. Hangings and draperies shall not be placed over exit doors or otherwise be located to conceal or obstruct an exit. Mirrors shall not be placed on exit doors. Mirrors shall not be placed in or adjacent to any exit in such a manner as to confuse the direction of exit.

***Remove curtains from exit door, ensure exit sign is fully visible.


RECEIVED: PRINT: ____________________________

SIGNATURE_________________________

RE-INSPECTION DATE_______


APPROVED______ NOT APPROVED______ INSPECTOR: CORRALES,B. MARSHAL: 26




CAPTAIN'S SIGNATURE______________________________