Case: T08FR00487

Parcel: 13213058A


Addresses:

1111 E BENSON HY

Inspection Status: Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/14/2008 INSP - FULL Violation 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
Remove all materials from in front of panels.
02/14/2008 INSP - FULL Violation 906.6 Unobstructed and unobscured. Fire extinguishers
shall not be obstructed or obscured from view. In rooms or areas
in which visual obstruction cannot be completely avoided,
means shall be provided to indicate the locations of
extinguishers.
906.7 Hangers and brackets. Hand-held portable fire
extinguishers, not housed in cabinets, shall be installed on the
hangers or brackets supplied. Hangers or brackets shall be securely
anchored to the mounting surface in accordance with the
manufacturer’s installation instructions.
Do not block any Fire Extinguishers.
02/14/2008 INSP - FULL Violation 703.1 Maintenance. The required fire-resistance rating of
fire-resistance-rated construction (including walls, fire stops,
shaft enclosures, partitions and floors) shall be maintained.
Such elements shall be properly repaired, restored or replaced
when damaged, altered, breached or penetrated. Openings
made therein for the passage of pipes, electrical conduit, wires,
ducts, air transfer openings, and holes made for any reason
shall be protected with approved methods capable of resisting
the passage of smoke and fire. Openings through fire-resistance-
rated assemblies shall be protected by self-closing or automatic-
closing doors of approved construction meeting the
fire protection requirements for the assembly.
703.1.1 Fireblocking and draftstopping. Required
fireblocking and draftstopping in combustible concealed
spaces shall be maintained to provide continuity and integrity
of the construction.
703.1.2 Smoke barriers. Required smoke barrier partitions
shall be maintained to prevent the passage of smoke and all
openings protected with approved smoke barrier doors or
leakage-rated (smoke) dampers.
Replace broken ceiling tiles.
02/14/2008 INSP - FULL Violation 1011.4 Internally illuminated exit signs. Internally illuminated
exit signs shall be listed and labeled and shall be installed
in accordance with the manufacturer’s instructions and Section
604. Exit signs shall be illuminated at all times.
Replace bulbs in Exit lights.
02/14/2008 INSP - FULL Violation 1027.2 Reliability. Required exit accesses, exits or exit discharges
shall be continuously maintained free from obstructions
or impediments to full instant use in the case of fire or
other emergency. Security devices affecting means of egress
shall be subject to approval of the fire code official.
1027.3 Obstructions. A means of egress shall be free from obstructions
that would prevent its use, including the accumulation
of snow and ice.
Do not block Exits.