Case: T08FR00386

Parcel: 14042063B


Addresses:

6681 S TUCSON BL


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T08FR00386

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
02/06/2008 INSP - FULL Violation
02/06/2008 INSP - FULL Violation 315.2 Storage in buildings. Storage of combustible materials
in buildings shall be orderly. Storage shall be separated from
heaters or heating devices by distance or shielding so that ignition
cannot occur.
315.2.1 Ceiling clearance. Storage shall be maintained 2
feet (610 mm) or more below the ceiling in nonsprinklered
areas of buildings or a minimum of 18 inches (457 mm) below
sprinkler head deflectors in sprinklered areas of buildings.

Do not store combustable materials in any equipment rooms.
02/06/2008 INSP - FULL Violation 510.1 Identification. Fire protection equipment shall be identified
in an approved manner. Rooms containing controls for
air-conditioning systems, sprinkler risers and valves, or other
fire detection, suppression or control elements shall be identified
for the use of the fire department. Approved signs required
to identify fire protection equipment and equipment location,
shall be constructed of durable materials, permanently installed
and readily visible.

Identify all fire equipment rooms.
02/06/2008 INSP - FULL Violation 605.4 Multiplug adapters. Multiplug adaptors, such as cube
adaptors, unfused plug strips or any other device not complying
with the ICC Electrical Code shall be prohibited.
605.4.1 Power tap design. Relocatable power taps shall be
of the polarized or grounded type, equipped with
overcurrent protection, and shall be listed.
605.4.2 Power supply. Relocatable power taps shall be directly
connected to a permanently installed receptacle.
605.4.3 Installation. Relocatable power tap cords shall not
extend through walls, ceilings, floors, under doors or floor
coverings, or be subject to environmental or physical damage.

Do not Piggyback strip plugs.
02/06/2008 INSP - FULL Violation 605.3.1 Labeling. Doors into electrical control panel rooms
shall be marked with a plainly visible and legible sign stating
ELECTRICAL ROOM or similar approved wording.
The disconnecting means for each service, feeder or branch
circuit originating on a switchboard or panelboard shall be
legibly and durably marked to indicate its purpose unless
such purpose is clearly evident.

Identify all equipment doors.
02/06/2008 INSP - FULL Violation 703.1 Maintenance. The required fire-resistance rating of
fire-resistance-rated construction (including walls, fire stops,
shaft enclosures, partitions and floors) shall be maintained.
Such elements shall be properly repaired, restored or replaced
when damaged, altered, breached or penetrated. Openings
made therein for the passage of pipes, electrical conduit, wires,
ducts, air transfer openings, and holes made for any reason
shall be protected with approved methods capable of resisting
the passage of smoke and fire. Openings through fire-resistance-
rated assemblies shall be protected by self-closing or automatic-
closing doors of approved construction meeting the
fire protection requirements for the assembly.
703.1.1 Fireblocking and draftstopping. Required
fireblocking and draftstopping in combustible concealed
spaces shall be maintained to provide continuity and integrity
of the construction.
703.1.2 Smoke barriers. Required smoke barrier partitions
shall be maintained to prevent the passage of smoke and all
openings protected with approved smoke barrier doors or
leakage-rated (smoke) dampers.
703.2 Opening protectives. Opening protectives shall be
maintained in an operative condition in accordance with NFPA
80. Fire doors and smoke barrier doors shall not be blocked or
obstructed or otherwise made inoperable. Fusible links shall be
replaced promptly whenever fused or damaged. Fire door assemblies
shall not be modified.

Seal all holes in any equipment,mechanical,electrical and Fire equipment rooms.