Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T08FR00294

Parcel: 140122150


Addresses:

5005 S CAMPBELL AV


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T08FR00294

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
01/28/2008 INSP - FULL Violation
01/28/2008 INSP - FULL Violation
01/28/2008 INSP - FULL Violation 315.2 Storage in buildings. Storage of combustible materials
in buildings shall be orderly. Storage shall be separated from
heaters or heating devices by distance or shielding so that ignition
cannot occur.
315.2.1 Ceiling clearance. Storage shall be maintained 2
feet (610 mm) or more below the ceiling in nonsprinklered
areas of buildings or a minimum of 18 inches (457 mm) below
sprinkler head deflectors in sprinklered areas of buildings.
315.2.2 Means of egress. Combustible materials shall not
be stored in exits or exit enclosures.
315.2.3 Equipment rooms. Combustible material shall not
be stored in boiler rooms, mechanical rooms or electrical
equipment rooms.
Do not store combustible materials in hot water heater area.
01/28/2008 INSP - FULL Violation 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
Do not block electrical pannel.
01/28/2008 INSP - FULL Violation 904.11.6.3 Cleaning. Hoods, grease-removal devices,
fans, ducts and other appurtenances shall be cleaned at
intervals necessary to prevent the accumulation of
grease. Cleanings shall be recorded, and records shall
state the extent, time and date of cleaning. Such records
shall be maintained on the premises.
Clean hood system every 3-months. Clean filters weekly. Not during business hours.
01/28/2008 INSP - FULL Violation 1006.3 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premise’s electrical supply.
In the event of power supply failure, an emergency electrical
system shall automatically illuminate the following areas:
1. Exit access corridors, passageways and aisles in rooms
and spaces which require two or more means of egress.
2. Exit access corridors and exit stairways located in buildings
required to have two or more exits.
3. Exterior egress components at other than the level of exit
discharge until exit discharge is accomplished for buildings
required to have two or more exits.
4. Interior exit discharge elements, as permitted in Section
1023.1, in buildings required to have two or more exits.
5. The portion of the exterior exit discharge immediately
adjacent to exit discharge doorways in buildings required
to have two or more exits.
The emergency power system shall provide power for a duration
of not less than 90 minutes and shall consist of storage
batteries, unit equipment or an on-site generator. The installation
of the emergency power system shall be in accordance with
Section 604.
Fix all emergency power lighting.
01/28/2008 INSP - FULL Violation 1011.5 Externally illuminated exit signs. Externally illuminated
exit signs shall comply with Sections 1011.5.1 through
1011.5.3.
1011.5.1 Graphics. Every exit sign and directional exit sign
shall have plainly legible letters not less than 6 inches (152
mm) high with the principal strokes of the letters not less
than 0.75 inch (19.1mm)wide. Theword “EXIT” shall have
letters having a width not less than 2 inches (51 mm) wide
except the letter “I,” and the minimum spacing between letters
shall not be less than 0.375 inch (9.5 mm). Signs larger
than the minimum established in this section shall have letter
widths, strokes and spacing in proportion to their height.
The word “EXIT” shall be in high contrast with the background
and shall be clearly discernible when the exit sign illumination
means is or is not energized. If an arrow is
provided as part of the exit sign, the construction shall be
such that the arrow direction cannot be readily changed.
1011.5.2 Exit sign illumination. The face of an exit sign illuminated
from an external source shall have an intensity of
not less than 5 foot-candles (54 lux).
1011.5.3 Power source. Exit signs shall be illuminated at
all times. To ensure continued illumination for a duration ofnot less than 90 minutes in case of primary power loss, the
sign illumination means shall be connected to an emergency
power system provided from storage batteries, unit equipment
or an on-site generator. The installation of the emergency
power system shall be in accordance with Section
604.
Exception: Approved exit sign illumination means that
provide continuous illumination independent of external
power sources for a duration of not less than 90 minutes,
in case of primary power loss, are not required to be connected
to an emergency electrical system.
Put bulbs in all non working exit lights.
01/28/2008 INSP - FULL Violation 315.1 General. Storage, use and handling of miscellaneous
combustible materials shall be in accordance with this section.
A permit shall be obtained in accordance with Section 105.6.
315.2 Storage in buildings. Storage of combustible materials
in buildings shall be orderly. Storage shall be separated from
heaters or heating devices by distance or shielding so that ignition
cannot occur.
315.2.1 Ceiling clearance. Storage shall be maintained 2
feet (610 mm) or more below the ceiling in nonsprinklered
areas of buildings or a minimum of 18 inches (457 mm) below
sprinkler head deflectors in sprinklered areas of buildings.
Do not store equipment, or any combustible materials on top of cooler.