Case: T08FR00293

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: VIOL - FLAMMABLE LIQUIDS

Case Number - T08FR00293

Inspection Description - VIOL - FLAMMABLE LIQUIDS

Inspection Status - Approved

Date Description Inspector Results Comments
02/11/2008 VIOL - FLAMMABLE LIQUIDS Approved Vents have been relocated to vent outdoors. Spark arrestors have been installed also.
01/28/2008 VIOL - FLAMMABLE LIQUIDS Correction Required 3404.2.7.3.3 Vent pipe outlets. Vent pipe outlets for tanks storing Class I, II or IIIA liquids shall be located such that the vapors are released at a safe point outside of buildings and not less than 12 feet (3658 mm) above the adjacent ground level. Vapors shall be discharged upward or horizontally away from adjacent walls to assist in vapor dispersion. Vent outlets shall be located such that flammable vapors will not be trapped by eaves or other obstructions and shall be at least 5 feet (1524 mm) from building openings or lot lines of properties that can be built upon.
ยท The vents to the two 100 gallon day tanks must vent to the outside of the building in accordance with the above code