Case: T08FR00266

Parcel: 124020810


Addresses:

1745 E 2ND ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
03/08/2008 VIOL - FIRE PROTECTION SYSTEMS Approved Approved.
01/25/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required ____Fire extinguishers not mounted to wall.

906.7 Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the
hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.

***Mount ALL fire extinguishers in house.
01/25/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required ____Annual sprinkler system test due.

901.6 Inspection, testing and maintenance.
Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

***Have system tested, and copy of results send to T.F.D.