Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T08FR00236
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/16/2010 | VIOL - MEANS OF EGRESS | Approved | ||
01/24/2008 | VIOL - MEANS OF EGRESS | Violation | TFC 1027.3 EXIT SIGN ILLUMINATION. ____REPAIR THE FOLLOWING EXIT SIGNS: NORTHEAST DOOR SOUTHEAST DOOR SOUTHWEST DOOR |
|
01/24/2008 | VIOL - MEANS OF EGRESS | Violation | TFC 1027.5 ILLUMINATION EMERGENCY POWER. IN THE EVENT OF POWER SUPPLY FAILURE, ILLUMINATION SHALL BE AUTOMATICALLY PROVIDED FROM AN EMERGENCY SYSTEM. ____REPLACE EXIT SIGNS WITH SIGNS THAT CONTAIN BATTERY BACKUP OR PROVIDE EXTERNAL EMERGENCY LIGHTING UNITS. |
|
01/24/2008 | VIOL - MEANS OF EGRESS | Violation | TFC 1028.8 PANIC HARDWARE. ____REMOVE ALL OTHER LOCKING DEVICES ON EXIT DOORS WITH PANIC HARDWARE. NORTHSIDE DOOR SOUTHEAST DOOR SOUTHWEST DOOR |