Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T08FR00188
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/06/2008 | INSP - FULL | Correction Required | 703.1.2 Smoke barriers. Required smoke barriers shall be maintained to prevent the passage of smoke and all openings protected with approved smoke barrier doors or smoke dampers. ___Replace ceiling tile |
|
02/06/2008 | INSP - FULL | Correction Required | 305.1 Clearance from ignition sources. Clearance between ignition sources, such as luminaires, heaters, flame-producing devices and combustible materials, shall be maintained in an approved manner. ___Remove combustibles from water heater area. |
|
02/06/2008 | INSP - FULL | Approved | All items corrected. Jan. 31, 2008 | |
01/17/2008 | INSP - FULL | Correction Required | 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. ___Maintain clearance in front of electrical panels |