Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR00187
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/06/2008 | INSP - FULL | Approved | All items corrected. Jan 31, 2008 | |
01/17/2008 | INSP - FULL | Correction Required | 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. ___Maintain 18" of clearance from sprinkler heads |
|
01/17/2008 | INSP - FULL | Correction Required | 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. ___Maintain clearance in front of electrical panels |
|
01/17/2008 | INSP - FULL | Correction Required | 1004.3 Posting of occupant load. Every room or space that is an assembly accupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ___ Provide Certificate of Occupancy |