Case: T08FR00178

Parcel: 12801005H

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00178

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2008 INSP - FULL Approved All corrected. Feb. 7, 2008.
01/16/2008 INSP - FULL Correction Required 605.4.2 Power supply. Relocatable power taps shall bedirectly connected to a permanently installed receptacle.
___Untangle multiplugs and cords.
01/16/2008 INSP - FULL Correction Required 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.
___Clear space in front of electrical panel
01/16/2008 INSP - FULL Correction Required 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
___Replace cover on outlet in back office
01/16/2008 INSP - FULL Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
___Replace ceiling tiles in back office
01/16/2008 INSP - FULL Correction Required 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.
___Maintain minimum of 18 inches clearance.