Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2008 | INSP - FULL | Approved | All items corrected | |
| 01/17/2008 | INSP - FULL | Correction Required | 308.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction. ___Store and use propane minimum of 10 feet from building. |
|
| 01/17/2008 | INSP - FULL | Correction Required | 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. ___Ensure all multi-plugs are plugged directly into outlets |
|
| 01/17/2008 | INSP - FULL | Correction Required | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 605.5.1 Power supply. Extension cords shall be plugged directly into an approved receptacle, power tap or multiplug adapter and, except for approved multiplug extension cords, shall serve only one portable appliance. ___Ensure extension cords are not plug into extension cords, and are not used for permanent appliances. |
|
| 01/17/2008 | INSP - FULL | Correction Required | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ___Cover all open junction boxes with appropriate covers and remove exposed, unconnected wiring. |
|
| 01/17/2008 | INSP - FULL | Correction Required | Section 316.1 General. (cot mod)Heating appliances shall be installed and maintained in accordance with their listing and the City of Tucson Building, Electrical, and Mechanical codes. Clearance from combustible material shall be maintained as set forth in the Building and Mechanical codes and the product listing. ___Remove combustibles from above and around water heater. |
|
| 01/17/2008 | INSP - FULL | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. ___Have hood system inspected and maintained. Replace nozzle caps. |
|
| 01/17/2008 | INSP - FULL | Correction Required | 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ___Remove surface bolts from rear door. |
|
| 01/17/2008 | INSP - FULL | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ___Replace double-keyed locks on rear exits with thumb latch locks on egress side. |
|
| 01/17/2008 | INSP - FULL | Correction Required | 2404.6 Smoking. Smoking shall not be permitted in tents, canopies or membrane structures. Approved “No Smoking” signs shall be conspicuously posted in accordance with Section 310. 2404.7 Open or exposed flame. Open flame or other devices emitting flame, fire or heat or any flammable or combustible liquids, gas, charcoal or other cooking device or any other unapproved devices shall not be permitted inside or located within 20 feet (6096 mm) of the tent, canopy or membrane structures while open to the public unless approved by the fire code official. ___Post "No Smoking" sign under canopy. Do not use open flame or heat producing devices within 20 feet of canopy. |
|
| 01/17/2008 | INSP - FULL | Correction Required | 2404.1 General. All tents, canopies and membrane structures, both temporary and permanent, shall be in accordance with this section. Permanent tents, canopies and membrane structures shall also comply with the International Building Code. 2404.2 Flame propagation performance treatment. Before a permit is granted, the owner or agent shall file with the fire code official a certificate executed by an approved testing laboratory certifying that the tents; canopies and membrane structures and their appurtenances; sidewalls, drops and tarpaulins; floor coverings, bunting and combustible decorative materials and effects, including sawdust when used on floors or passageways, shall be composed of material meeting the flame propagation performance criteria of NFPA 701 or shall be treated with a flame retardant in an approved manner and meet the flame propagation performance criteria of NFPA 701, and that such flame propagation performance criteria are effective for the period specified by the permit. 2404.3 Label. Membrane structures, tents or canopies shall have a permanently affixed label bearing the identification of size and fabric or material type. 2404.4 Certification. An affidavit or affirmation shall be submitted to the fire code official and a copy retained on the premises on which the tent or air-supported structure is located. The affidavit shall attest to the following information relative to the flame propagation performance criteria of the fabric: 1. Names and address of the owners of the tent, canopy or air-supported structure. 2. Date the fabric was last treated with flame-retardant solution. 3. Trade name or kind of chemical used in treatment. 4. Name of person or firm treating the material. 5. Name of testing agency and test standard by which the fabric was tested. ___Remove canopy or have covering treated or replaced with approved covering. |
|
| 01/17/2008 | INSP - FULL | Correction Required | 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints. 2. Securing containers, cylinders and tanks on a cart or other mobile device designed for the movement of compressed gas containers, cylinders or tanks. 3. Nesting of compressed gas containers, cylinders and tanks at container filling or servicing facilities or in seller’s warehouses not accessible to the public. Nesting shall be allowed provided the nested containers, cylinders or tanks, if dislodged, do not obstruct the required means of egress. 4. Securing of compressed gas containers, cylinders and tanks to or within a rack, framework, cabinet or similar assembly designed for such use. ___Secure all compressed gas cylinders. |
|
| 01/11/2008 | INSP - FULL | Correction Required | BMERRIT1 ASSIGNED. | |
| 01/11/2008 | INSP - FULL | Correction Required | Requesting a fire inspection for his business please contact Jeff at 250-6504. Business name is North Shore |