Case: T08FR00091

Parcel: 11807238A


Addresses:

1702 W 36TH ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00091

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
03/07/2008 INSP - FULL Approved Manager stated that while padlock is on order, The access gate will remain open at all times for a trial period of 30 days. If there is no rise in criminal activity, it will remain open at all times. If gate needs to be shut, it will remain OPEN until padlock is installed.
01/09/2008 INSP - FULL Correction Required Recieved phone call from E15A regarding apparatus access in an apartment complex.
01/09/2008 INSP - FULL Correction Required On 1-8-08, responded to scene. Noticed that padlocked gate interrupted FD access with no area to turn around apparatus. Dead ends in fire department access roads in excess of 150 ft. in length shall be provided with an approved area for turning around fire apparatus. 2006 IFC 503.2.5

2006 IFC 503.6 SECURITY GATES- Where security gates are installed, they shall have an approved means of emergency operation. Gates and emergency operation shall be maintained operational at all times.

***Ensure instant emergency access at ALL times, via a keybox or Fire Department padlock.