Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2008 | VIOL - FIRE PROTECTION SYSTEMS | Approved | all o.k. 2/6. | |
| 01/16/2008 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | ____Sprinkler system due for annual test. ____Fire extinguishers due for annual test. ____Smoke detector log shall be filled out, returned to T.F.D. 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ***Have system/extinguishers tested immediately. |
|
| 01/16/2008 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | ____Fire extinguisher needs to be mounted in Rec room. 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ***Mount extinguisher. |
|
| 01/16/2008 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | ____Fire Dept. Connections (FDC's) need caps on inlets. 912.6 Inspection, testing and maintenance. All fire department connections shall be periodically inspected, tested and maintained in accordance with NFPA 25. ***Install caps on FDC's. |