Case: T08FR00088

Parcel: 12402083E


Addresses:

1030 N MARTIN AV

Inspection Status: Approved

Inspection History: VIOL - FIRE SERVICE FEATURES

Date Description Inspector Results Comments
02/06/2008 VIOL - FIRE SERVICE FEATURES Approved all o.k. 2/6.
01/16/2008 VIOL - FIRE SERVICE FEATURES Correction Required ____Riser room unlabeled, accessible only from the outside.

510.1 Identification
Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air conditioning, sprinkler risers and valves, or other fire detection, suppression, or control elements shall be identified for use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
***Install permanent sign reading: "Riser Room".
01/16/2008 VIOL - FIRE SERVICE FEATURES Correction Required ____Chairlift shaftway unlabeled.

507.2.2 Interior access to shaftways. Door or window
openings to a hoistway or shaftway from the interior of the
building shall be plainly marked with the word
SHAFTWAY in red letters at least 6 inches (152 mm) high
on a white background. Such warning signs shall be placed
so as to be readily discernible.
***Install sign on upper/lower shaftway doors.