Inspection Status: Approved
Inspection History: VIOL - FIRE SERVICE FEATURES
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2008 | VIOL - FIRE SERVICE FEATURES | Approved | all o.k. 2/6. | |
| 01/16/2008 | VIOL - FIRE SERVICE FEATURES | Correction Required | ____Riser room unlabeled, accessible only from the outside. 510.1 Identification Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air conditioning, sprinkler risers and valves, or other fire detection, suppression, or control elements shall be identified for use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. ***Install permanent sign reading: "Riser Room". |
|
| 01/16/2008 | VIOL - FIRE SERVICE FEATURES | Correction Required | ____Chairlift shaftway unlabeled. 507.2.2 Interior access to shaftways. Door or window openings to a hoistway or shaftway from the interior of the building shall be plainly marked with the word SHAFTWAY in red letters at least 6 inches (152 mm) high on a white background. Such warning signs shall be placed so as to be readily discernible. ***Install sign on upper/lower shaftway doors. |