Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR00073
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/29/2008 | INSP - FULL | Approved | All corrected. | |
01/07/2008 | INSP - FULL | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. C102.6.1 - Inspection 2. Sprinklers shall be free of corrosion, foreign materials, paint and physical damage and shall be installed in the proper orientation. ___ Clean sprinkler head |
|
01/07/2008 | INSP - FULL | Correction Required | 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. ___Clearance from sprinkler is 18" for storage |
|
01/07/2008 | INSP - FULL | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire resistant joint systems) shall be maintained. ___Repair or replace ceiling tile |
|
01/07/2008 | INSP - FULL | Correction Required | 1014.1.1 Aisles in Groups B and M. In Group B and M ocupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches. Exception: Nonpublic aisles serving less than 50 people and not required to be accessible by Chapter 11 of the International Building Code need not exceed 28 inches in width. ___ Clear access in storage room |