Case: T08FR00061

Parcel: 128010400


Addresses:

1108 S WILMOT RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/06/2008 INSP - FULL Approved All corrected. Feb. 06, 2008
01/04/2008 INSP - FULL Correction Required 110.1 General. If during the inspection of a premises, a building or structure or any building system, in whole or in part, constitutes a clear and inimical threat to human life, safety or health, the fire code official shall issue such notice or orders to remove or remedy the conditions as shall be deemed necessary in accordance with this section and shall refer the building to the building department for any repairs, alterations, remodeling, removing or demolition required.
110.1.1 Unsafe conditions. Structures or existing equipment that are or hereafter become unsafe or deficient because of inadequate means of egress or which constitute a fire hazard, or are otherwise dangerous to human life or the public welfare, or which involve illegal or improper occupancy or inadequate maintenance, shall be deemed a unsafe condition.
504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. Required fire department access doors shall not be obstructed or eliminated. Exit and exit access doors shall comply with Chapter 10.
___Rear Wall and Door need to be made structurally sound and functional in accordance with all applicable codes. Until repairs are made, signage stating "No Exit" shall be posted on interior and "This Door Blocked" on the exterior. Issue will be referred to building services department.
01/03/2008 INSP - FULL Correction Required 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
___Remove extension cord to computer.
01/03/2008 INSP - FULL Correction Required 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
___Replace covers on 3 outlets on north wall.
01/03/2008 INSP - FULL Correction Required 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
906.5 Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for
placement away from normal paths of travel.
906.6 Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers.
___Have extinguisher inspected or removed from facility (IAW Tucson Fire Code 906.1).
01/03/2008 INSP - FULL Correction Required 1004.3 Posting of occupant load. Every room or space that is an assembly accupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
___ No Certificate of Occupancy