Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2008 | INSP - FULL | Approved | All violations corrected. 1-10-2008 | |
| 01/04/2008 | INSP - FULL | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ___Replace double keyed deadbolts with thumb-turn latches. |
|
| 01/03/2008 | INSP - FULL | Correction Required | 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. ___Plug multiplug powerstrip directly into receptacle, not into other powerstrip. |
|
| 01/03/2008 | INSP - FULL | Correction Required | 1004.3 Posting of occupant load. Every room or space that is an assembly accupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ___ Provide Certificate of Occupancy |
|
| 01/03/2008 | INSP - FULL | Correction Required | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. ___Remove extension cord from lighting over front counter. |