Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T08FR00017
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/15/2008 | VIOL - MEANS OF EGRESS | Approved | Clear- good job / Lock removed on door - good job | |
01/02/2008 | VIOL - MEANS OF EGRESS | Violation | Blocked exit: 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _______Clear exit area, and maintain it this way.[By back roll up] |
|
01/02/2008 | VIOL - MEANS OF EGRESS | Violation | Panic Hardware: IFC2006 [TFC with modifications] / 1028.8 Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. ______Remove bolt lock. [SW door] Re-inspection date scheduled on or after Jan 17th, 2008. If you have any questions or concerns please call Inspector Cobb at 791-4502 Thank you, _____________________________________________ Brian Cobb, Inspector, Tucson Fire Department __________________________I have received a copy of this inspection report. Building Representative _____________________________________________ Captain |