Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/18/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/13/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* LOCKED NO ACCESS |
|
| 01/08/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) MAINTAIN WORKING CLEARANCES AT DISCONNECT 110.26 2) CLEAN SURFACE UNDER LUG 250.12 3) LABEL CIRCUIT DIRECTORY 408.4 4) INSTALL BREAKER |