Permit: T08EL02301

Parcel: 116123280


Addresses:

1432 W DELAWARE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/13/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/05/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS 9:34 AM-RECALL
12/23/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) GROUNDED RECEPTS THRU-OUT, NEW ROMEX WITH GROUND RUN THRU-OUT, NO GRD AT SUB PANEL. 3 WIRES RUN FROM SERVICE ONLY. NEED A GROUND AT SUB-PANEL, ISOLATE NEUTRALS/GRDS
2) FURNACE 2 SETS OF BREAKERS 30/30-60/60, 50/50 CIRCUIT TO FURNACE FROM SUB-PANEL #8 CU.
3) ELECTRIC FURNACE NOT CONNECTED FROM DISCONNECT