Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/05/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ACCESS 9:34 AM-RECALL |
|
| 12/23/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) GROUNDED RECEPTS THRU-OUT, NEW ROMEX WITH GROUND RUN THRU-OUT, NO GRD AT SUB PANEL. 3 WIRES RUN FROM SERVICE ONLY. NEED A GROUND AT SUB-PANEL, ISOLATE NEUTRALS/GRDS 2) FURNACE 2 SETS OF BREAKERS 30/30-60/60, 50/50 CIRCUIT TO FURNACE FROM SUB-PANEL #8 CU. 3) ELECTRIC FURNACE NOT CONNECTED FROM DISCONNECT |