Permit: T08EL02270

Parcel: 129041750

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL02270

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
12/15/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE DISCONNECT MUST BE MARKED OR TAGGED WITH PERMANENT LABEL, SCREWED OR RIVETED TO ENCLOSURE MARKER PEN NOT ACCEPTABLE -- 110.32 NEC
2. BLD. LOCKED; NO MSG.
12/11/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PERMIT TO BE POSTED ON SITE
2. LABEL SERVICE DISCONNECT FOR THIS TENANT

RECALL INSP. WHEN DONE