Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2012 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 02/09/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* ISOLATE GROUNDS & NEUTRALS AT SUB PANEL NEUTRAL TO BE RUN TO SUB-PANEL |
|
| 12/13/2011 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER TIE IN |
|
| 12/06/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SPLICE ON GEC TO BE IRREVERSIBLE TYPE PER 250 NEC 2) CIRCUIT BREAKERS TO BE OF SAME MANUFACTURE AS PANEL 110.3 NEC 3) SUPPORT #4 BARE TO STRUCTURE |