Permit: T08EL02264

Parcel: 129054620


Addresses:

2913 E 19TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/01/2012 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
02/09/2012 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
ISOLATE GROUNDS & NEUTRALS AT SUB PANEL
NEUTRAL TO BE RUN TO SUB-PANEL
12/13/2011 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) CALL FOR FINAL AFTER TIE IN
12/06/2011 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SPLICE ON GEC TO BE IRREVERSIBLE TYPE PER 250 NEC
2) CIRCUIT BREAKERS TO BE OF SAME MANUFACTURE AS PANEL 110.3 NEC
3) SUPPORT #4 BARE TO STRUCTURE