Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/03/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* NO PERMIT CARD TO SIGN OFF ON |
|
| 12/31/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO LEAVE PERMIT CARD ON JOB SITE (YELLOW CARD) |
|
| 12/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO EXPOSE GROUND RODS TO VERIFY CONTINOUS GROUND 2) GROUND RODS MUST BE A MINIMUM 6' APART OR BE ABLE TO PROVE THAT SERVICE HAS 25 OHMS TO GROUND 3) NO PERMIT ON SITE |
|
| 12/17/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) EXPOSE GROUND RODS 2) COMPLETE WATER AND GAS BOND |