Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T08EL02233

Parcel: 12913210C


Addresses:

1201 E 33RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/03/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
NO PERMIT CARD TO SIGN OFF ON
12/31/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO LEAVE PERMIT CARD ON JOB SITE (YELLOW CARD)
12/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO EXPOSE GROUND RODS TO VERIFY CONTINOUS GROUND
2) GROUND RODS MUST BE A MINIMUM 6' APART OR BE ABLE TO PROVE THAT SERVICE HAS 25 OHMS TO GROUND
3) NO PERMIT ON SITE
12/17/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) EXPOSE GROUND RODS
2) COMPLETE WATER AND GAS BOND