Permit: T08EL02227

Parcel: 117050630


Addresses:

403 N 6TH AV #143

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/19/2010 ELECTRIC - FINAL Approved
11/03/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT EXIT SIGN CONDUITS
2) SUPPORT CONDUITS AS PER CODES
3) FILL UNUSED OPENINGS IN BOXES
4) SUPPORT M/C CABLE TO TRAC LIGHTS
5) NEED TO VERIFY LOAD CALCULATIONS FOR TRAC LIGHTING
6) PLEASE PROVIDE ROOF ACCESS
7) DIMMERS OVER HEATING-VERIFY LOADS, CONDUCTOR FILL AND DERATING
8) PLEASE HAVE OLD WRITE UPS ON SITE
06/10/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLEASE VERIFY PERMITS FOR STRUCTURAL, PLUMBING AND MECHANICAL
2. FINISH PREVIOUS ITEMS MARKED
06/02/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS
2. SUPPORT CONDUITS AS PER CODE
3. USE CORRECT SIZE STRAPS
4. BOXES OVERFILLED
5. PROTECT CONDUCTORS AT LIGHT
02/13/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOND SERVICE NIPPLES 250.92
2. BOND UNGROUNDED CONDUCTOR TO GROUNDING ELECTRODE CONDUCTOR 250.24
3. PLANS NOT REFLECTIVE OF WORK INSTALLED