Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL02226
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2010 | ELECTRIC - FINAL | Approved | ||
11/03/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT EXIT SIGN CONDUITS 2) SUPPORT CONDUITS AS PER CODES 3) FILL UNUSED OPENINGS IN BOXES 4) SUPPORT M/C CABLE TO TRAC LIGHTS 5) NEED TO VERIFY LOAD CALCULATIONS FOR TRAC LIGHTING 6) PLEASE PROVIDE ROOF ACCESS 7) DIMMERS OVER HEATING-VERIFY LOADS, CONDUCTOR FILL AND DERATING 8) PLEASE HAVE OLD WRITE UPS ON SITE |
|
06/10/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE VERIFY PERMITS FOR STRUCTURAL, PLUMBING AND MECHANICAL 2. FINISH PREVIOUS ITEMS MARKED |
|
06/02/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL SCHEDULE NOT LEGIBLE 408.4 2. TIGHTEN LOOSE FITTINGS 3. SUPPORT CONDUIT AS PER CODE 4. SUPPORT EXIT LIGHT CONDUIT 5. NO MORE THAN 360 DEG. IN A CONDUIT RUN 6. MISSING COVER PLATES |
|
02/13/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOND SERVICE NIPPLES 250.92 2. BOND UNGROUNDED CONDUCTOR TO GROUNDING ELECTRODE CONDUCTOR 250.24 3. PLEASE REVISE PLAN TO REFLECT WORK INSTALLED |