Permit: T08EL02223

Parcel: 117050630


Addresses:

403 N 6TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL02223

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/19/2010 ELECTRIC - FINAL Approved
11/03/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT EXIT SIGN CONDUITS
2) SUPPORT CONDUITS AS PER CODES
3) FILL UNUSED OPENINGS IN BOXES
4) SUPPORT M/C CABLE TO TRAC LIGHTS
5) NEED TO VERIFY LOAD CALCULATIONS FOR TRAC LIGHTING
6) PLEASE PROVIDE ROOF ACCESS
7) DIMMERS OVER HEATING-VERIFY LOADS, CONDUCTOR FILL AND DERATING
8) PLEASE HAVE OLD WRITE UPS ON SITE
06/10/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLEASE VERIFY PERMITS FOR STRUCTURAL, PLUMBING AND MECHANICAL
2. FINISH PREVIOUS ITEMS MARKED
06/02/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES OVERFILLED
2. SUPPORT EXIT LIGHT CONDUIT
3. SUPPORT CONDUIT AS PER CODE
4. EXIT LIGHTS TO BE AS PER 700.12(F)
5. PANEL SCHEDULE NOT LEGIBLE (408.4)
6. BOX OVERFILLED
7. FILL UNUSED OPENING AND MISSING COVER PLATES
8. TIGHTEN LOOSE FITTINGS
02/13/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
A BOND WILL BE NEEDED FOR POWER - TEMP FOR TEST

1. BOND SERVICE NIPPLES 250.92
2. BOND UNGROUNDED CONDUCTOR TO GROUNDING ELECTRODE CONDUCTOR 250.24
3. PLEASE REVISE PLAN TO MATCH WORK INSTALLED
12/12/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ONE ON SITE WITH KNOWLEDGE OF WORK
NO PLANS OR PERMIT ON SITE
POST ADDRESS ON BUILDING