Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL02223
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2010 | ELECTRIC - FINAL | Approved | ||
11/03/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT EXIT SIGN CONDUITS 2) SUPPORT CONDUITS AS PER CODES 3) FILL UNUSED OPENINGS IN BOXES 4) SUPPORT M/C CABLE TO TRAC LIGHTS 5) NEED TO VERIFY LOAD CALCULATIONS FOR TRAC LIGHTING 6) PLEASE PROVIDE ROOF ACCESS 7) DIMMERS OVER HEATING-VERIFY LOADS, CONDUCTOR FILL AND DERATING 8) PLEASE HAVE OLD WRITE UPS ON SITE |
|
06/10/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE VERIFY PERMITS FOR STRUCTURAL, PLUMBING AND MECHANICAL 2. FINISH PREVIOUS ITEMS MARKED |
|
06/02/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES OVERFILLED 2. SUPPORT EXIT LIGHT CONDUIT 3. SUPPORT CONDUIT AS PER CODE 4. EXIT LIGHTS TO BE AS PER 700.12(F) 5. PANEL SCHEDULE NOT LEGIBLE (408.4) 6. BOX OVERFILLED 7. FILL UNUSED OPENING AND MISSING COVER PLATES 8. TIGHTEN LOOSE FITTINGS |
|
02/13/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* A BOND WILL BE NEEDED FOR POWER - TEMP FOR TEST 1. BOND SERVICE NIPPLES 250.92 2. BOND UNGROUNDED CONDUCTOR TO GROUNDING ELECTRODE CONDUCTOR 250.24 3. PLEASE REVISE PLAN TO MATCH WORK INSTALLED |
|
12/12/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ONE ON SITE WITH KNOWLEDGE OF WORK NO PLANS OR PERMIT ON SITE POST ADDRESS ON BUILDING |