Date Description Inspector Results Comments
01/06/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/05/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH #3 & #5 PREVIOUS INSPECTION
SEALING LOCKNUT AND BOND BUSHING
12/30/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) AN APPROVED MAST BRACE
2) SERVICE NIPPLE NOT PER 230.7
3) BOND SERVICE NIPPLE 250.92
4) PLEASE VERIFY LAST SERVICE UPGRADE PERMIT
5) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH APPROVED