| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/05/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH #3 & #5 PREVIOUS INSPECTION SEALING LOCKNUT AND BOND BUSHING |
|
| 12/30/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) AN APPROVED MAST BRACE 2) SERVICE NIPPLE NOT PER 230.7 3) BOND SERVICE NIPPLE 250.92 4) PLEASE VERIFY LAST SERVICE UPGRADE PERMIT 5) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH APPROVED |