Permit: T08EL02173

Parcel: 130050230


Addresses:

1826 S OLSEN AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/09/2009 ELECTRIC - FINAL Denied 1) IN SUB-PANEL ISOLATE GROUNDS AND NEUTRALS
2) INSTALL GROUND BUSS
3) REMOVE BOND TO NEUTRAL
01/08/2009 ELECTRIC - FINAL Denied 1) GROUND FROM SUB-PANEL MUST GO TO SERV. PANEL, NOT A GROUND ROD
2) ANY QUESTION CALL RAY MAJUTA
01/06/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) #2 ABOVE REF. H20 HTR, GAS METER LOCKED OUT WILL BE HANDLED AT GAS RECONNECT INSP, COMB/RELIEF ETC...
2) UPGRADED SUB-PANEL, UNDERGROUNDED SYSTEM. YOU CANNOT RUN GROUNDED CIRCUITS FROM THIS PANEL UNLESS YOU RUN A GROUNDING CONDUCTOR BACK TO SERVICE PANEL
3) ALL GROUNDED RECEPTS IN HOUSE MUST BE ON A GROUND CIRCUIT, OR TO BE A GFCI RECEPTACLE
4) DRYER CIRCUIT BOND AT CONCENTRIC K.O. NOT SUFFICIENT RUN 4 GRD WIRE
5) NO WASHER CIRCUIT INSTALLED
6) COOLER CIRCUIT IS TAPPED AT KIT DOOR AREA SIDE YARD WHERE DOES TAP GO ?
7) UNDER SINK SOMEONE PLUMBEDTRAP ARM INCORRECTLY S-TRAP
8) ROMEX EXPOSED IN STUCCO AT REAR SERVICE PANEL
9) A/C WINDOW UNIT TO HAVE IT'S OWN CIRCUIT
12/31/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) UNABLE TO LOCATE 60 AMP SUB-PANEL, OR H20 HTR
2) GAS LINE FLEX CUT IN HALL CLOSET
3) WIRE IN SERVICE PANEL WITH ELECTRIC TAPE TO PROTECT END
4) DOOR LOCKED TO STORAGE ON NORTH SIDE
11/20/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*