Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2009 | ELECTRIC - FINAL | Denied | 1) IN SUB-PANEL ISOLATE GROUNDS AND NEUTRALS 2) INSTALL GROUND BUSS 3) REMOVE BOND TO NEUTRAL |
|
| 01/08/2009 | ELECTRIC - FINAL | Denied | 1) GROUND FROM SUB-PANEL MUST GO TO SERV. PANEL, NOT A GROUND ROD 2) ANY QUESTION CALL RAY MAJUTA |
|
| 01/06/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) #2 ABOVE REF. H20 HTR, GAS METER LOCKED OUT WILL BE HANDLED AT GAS RECONNECT INSP, COMB/RELIEF ETC... 2) UPGRADED SUB-PANEL, UNDERGROUNDED SYSTEM. YOU CANNOT RUN GROUNDED CIRCUITS FROM THIS PANEL UNLESS YOU RUN A GROUNDING CONDUCTOR BACK TO SERVICE PANEL 3) ALL GROUNDED RECEPTS IN HOUSE MUST BE ON A GROUND CIRCUIT, OR TO BE A GFCI RECEPTACLE 4) DRYER CIRCUIT BOND AT CONCENTRIC K.O. NOT SUFFICIENT RUN 4 GRD WIRE 5) NO WASHER CIRCUIT INSTALLED 6) COOLER CIRCUIT IS TAPPED AT KIT DOOR AREA SIDE YARD WHERE DOES TAP GO ? 7) UNDER SINK SOMEONE PLUMBEDTRAP ARM INCORRECTLY S-TRAP 8) ROMEX EXPOSED IN STUCCO AT REAR SERVICE PANEL 9) A/C WINDOW UNIT TO HAVE IT'S OWN CIRCUIT |
|
| 12/31/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UNABLE TO LOCATE 60 AMP SUB-PANEL, OR H20 HTR 2) GAS LINE FLEX CUT IN HALL CLOSET 3) WIRE IN SERVICE PANEL WITH ELECTRIC TAPE TO PROTECT END 4) DOOR LOCKED TO STORAGE ON NORTH SIDE |
|