Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2009 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 01/08/2009 | ELECTRIC - RECONNECT | Denied | ||
| 01/06/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/31/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/21/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OMIT HAZARDOUS ELECTRICAL TO FRONT FIXTURE AND CARPORT CEILING FAN 2) 90 DEGREE FITTING PRESSURE RELIEF VALVES REPLACE FLUE LINE WATER HEATER 3) WEATHERED FIXTURE EXTERIOR DOOR NORTH 4) PROVIDE WEATHERED FITTINGS EXTERIOR ADDED CIRCUITS 5) REMOVE ALL ADDED CIRCUITS TO PANEL OR PERMIT AND INSTALL TO CODE 6) EXPOSED WIRING KITCHEN WALLS AND CEILING 7) MISSING COVER PLATES THROUGHOUT 8) GFCI PROTECT KITCHEN OUTLETS 9) ALL BEDROOM WINDOWS MUST OPEN FREELY FOR EMERGENCY EGRESS 10) OUTLETS CHANGED FROM 2 WIRE TO GROUNDED OUTLETS GFCI PROTECT OR CHANGE BACK 11) SMOKE DETECTORS BEDROOMS 12) GFCI PROTECT BATH OUTLETS 13) STOPPED INSPECTION |
|
| 11/20/2008 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* 1) INSPECTOR NEEDS ACCESS TO INTERIOR OF HOUSE TO PERFORM INSPECTION 2) PLEASE RE-CALL WHEN ACCESS IS AVAILABLE |