Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL02079
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/18/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED SERVICE RISER GUY WIRE STRAP TO BE 1' FROM WEATHERHEAD LOOK AT EXISTING UNLESS TEP PROVIDES? 2. NEED 30A AND 40A FUSED DISCONNECTS FOR AC's 3. NEED SERVICE OUTLET FOR AC's 25' MAX. 4. NEED BLACK INSULATION WIRE FOR AC NOT WHITE WITH YELLOW TAPE 5. GAS LINE NEEDS TO BE 3' AWAY FROM FRONT OF DISCONNECT 6. CLEAN BOTTOMO OF METER BASE AND PANEL |