Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL02066
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST UNIT NUMBER 2) OMIT OUTLETS SOUTH EXT. WALL OR PROTECT FROM PHYSICAL DAMAGE 3) BLANK COVER PEDESTAL DEAD FRONT 4) INSTALL STEPS BOTH DOORS. FRONT DOOR STEPS NOT TO CODE 5) PROTECT ROMEX FRONT LIGHT FIXTURES FROM PHYSICAL DAMAGE 6) GFCI PROTECT KITCHEN OUTLETS |