Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2008 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 11/05/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 60 AMP MAIN DISCONNECT AT WEST UNIT, HAS BEEN LABELED 2) ALL NEUTRALS AND GRDS SEEM TO BE CONNECTED TO AN ISOLATED BUSS BAR IN SUB-PANEL, WITHOUT A GRD FOR SAME SUB-PANEL. I DON'T KNOW IF THIS IS UNIQUE TO THIS UNIT, OR THEY ARE ALL WIRED THIS WAY. NUETRALS SHOULD BE ISOLATED. IF ANY FURTHER QUESTIONS PLEASE CALL ME OR RAY MAJUTA HEAD ELECT. INSPECTOR. I SPOKE TO HIM ABOUT THIS, PROTECT ROMEX IN STOREROOM 3) REPLACE ALL CU. THAT HAS BEEN VANDALIZED FOR H20 SYSTEM |
|
| 10/31/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |